JN22-40.5/31.5 Indoor Grounding Switch

N22-40.5/31.5 indoor grounding switch is suitable for three-phase power system with rated voltage of 40.5kV and AC 50Hz. It can be used with KYN61-40.5 high-voltage switchgear and other types of high-voltage switchgear as grounding protection during maintenance of high-voltage electrical equipment.
Email to Us

Overview


N22-40.5/31.5 indoor grounding switch is suitable for three-phase power system with rated voltage of 40.5kV and AC 50Hz. It can be used with KYN61-40.5 high-voltage switchgear and other types of high-voltage switchgear as grounding protection during maintenance of high-voltage electrical equipment.

 

Operating Conditions


1. Altitude: ≤ 1000 meters;

2. The environment temperature: upper limit +40℃, lower limit -25℃;

3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;

4. Earthquake intensity: ≤8degree;

5. Class of pollution: II

 

Model and meaning


 

Technical Data


Item Unit Parameter
Rated voltage kV 40.5
Rated short time withstand current kA 31.5
Rated short circuit withstand time s 4
Rated short circuit making current kA 80
Rated peak withstand current kA 80
Rated insulation level 1min power frequency withstand voltage kV 95
Lightning impulse withstand voltage 185
Central distance between poles mm 300/350/400

 

Overall and mounting dimensions(mm)