FZN21-12 Load Switch

FZN21-12 load switch and combination device are used in three-phase AC 12kV, 50Hz distribution systems. They have the advantages of compact structure, small size, light weight, long service life, strong closing and breaking ability, safety and reliability. When used in conjunction with fuses, they can replace expensive circuit breakers, and their operation and maintenance are simple and convenient.
Email to Us

Overview


FZN21-12 load switch and combination device are used in three-phase AC 12kV, 50Hz distribution systems. They have the advantages of compact structure, small size, light weight, long service life, strong closing and breaking ability, safety and reliability. When used in conjunction with fuses, they can replace expensive circuit breakers, and their operation and maintenance are simple and convenient.

 

Operating Conditions


1. Altitude: ≤ 1000 meters

2. The environment temperature: upper limit +40℃, lower limit -25℃

3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%;

4. There is no fire, explosion hazard, serious pollution, Places subject to chemical corrosion and severe vibration.

 

Model and meaning


 

Technical Data


Item Unit Parameter
Technical parameters of vacuum load switch
Rated voltage kV 12
Rated frequency Hz 50
Rated current A 630
Rated active load breaking current 630
Rated close loop breaking current 630
5% at rated load breaking current 31.5
Rated cable charging breaking current 10
Interrupting no load transformer capacity kVA 1250
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) kV 42/48
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) 75/85
4s rated short-time withstand current kA 20
Rated peak withstand current 50
Rated short-circuit closing current 50
Mechanical life Times 10000
Allowable cumulative thickness wear in contact mm 2
Opening and closing operating torque N/m ≤200
Technical parameter of combinations
Rated voltage kV 12
Rated frequency Hz 50
The maximum rated current of the fuse A 125
The fuse triggered switch segment time ms 40±5
Rated short-circuit breaking current kA 31.5
Rated short-circuit closing current 50
1min power frequency withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) kV 42/48
The lightning impulse withstand voltage (vacuum fracture, interphase, phase to earth / isolation fracture) 75/85

 

Overall and mounting dimensions(mm)



1.Cabinet bracket

2.Disconnector

3.Fuse

4.Insulated tension pole

5.Upper bracket

6.Vacuum interrupter

7.Static contact

8.Insulator

9.Grounding knife

10.Grounding knife spring

11.Opening spring

12.Insulated tension

13.Main axle

14.The tripping driving device

15.Layshaft

16.Adjusting yoke

17.Operating mechanism